RCQD ATS for Swift Power Transfers up to 63A

The RCQD Series PC-Grade Automatic Transfer Switch ensures continuous power. Designed for 6A to 63A loads, it offers high reliability, DIN-rail mounting, and robust IP30 protection for seamless backup power in critical applications.

    Description

    The RCQD Series Dual Power Automatic Transfer Switch (ATS) is
    a PC-grade automatic transfer switch designed for AC 50-60Hz
    systems with a rated current from 6A to 63A. It features a two-position design (common and standby) to automatically transfer
    the load to a backup power source in the event of a main power
    failure, ensuring continuous operation with a swift transfer time of
    less than 50 milliseconds.

    Feature

    ● Swift automatic transfer with operation time under 50ms
    ● Rated operational current from 6A to 63A (2P/4P)
    ● High reliability with a mechanical life of ≥ 5000 cycles
    ● DIN-rail mounting for easy installation
    ● Robust protection: case rating of IP30 and impulse withstand
    voltage of 8kV
    ● Supports both manual and automatic operation modes

    Technical parameters

    Model and Specification RCOD
    Case grade 63 grade
    Rated operating current Ie(A) 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A
    Rated insulation voltage Ui 690V
    Rated impulse withstand voltage Uimp 8kV
    Rated working voltage Ue AC220VAC110V
    Rated frequency 50/60Hz
    Class Pc class, can be switched on an loaded without generating short-circuit current
    Pole number 2P, 4P
    Rated short-circuit current Iq 50kA
    Short circuit protection device (fuse) RT16 - 00 - 63A
    Rated impulse withstand voltage 8kV
    Control circuit Rated control voltage Us: AC220V, 50Hz; Normal working conditions: 85%Us - 110%Us
    Auxiliary circuit AC220V/110V, 50Hz Ie = 5A
    Contact change-over time
    Operation change-over time
    Return change-over time
    Power off time
    Change-over operation time
    Mechanical life ≥5000 Times
    Electrical life ≥15000 Times
    Rated insulation voltage Ui 690V
    Usage category AC - 31B

    Wiring Instructions

    11