Leave Your Message
Products Categories
Featured Products

Modular VFD Drive: 150% Overload & Sensorless Vector Control for Industrial Motors

The High-performance Vector Frequency Converter delivers precise motor control for industrial applications. Utilizing advanced sensorless vector (SVC) and V/F technology, it ensures high torque (1150% at 0.5Hz) and stable operation across variable loads. Designed for indoor use, it integrates seamlessly into automation systems with flexible command sources, PID control, and robust protection.

    Feature

    1. Advanced Control: Sensorless vector (SVC) and V/F modes with 1:100 speed range and 150% overload capacity.
    2. Versatile Operation: Supports multi-speed control (16 segments), PID regulation, and automatic voltage stabilization (AVR).
    3. Durable Design: Compact, stackable installation; operates at -10°C to 40°C with altitude derating up to 3000m.
    4. Smart Integration: RS485/Modbus-RTU communication, dual-digital display, and brake-ready models (B-series).
    5. Comprehensive Protection: Phase-loss, short-circuit, overheat, and ground-fault safeguards.

    Technical Parameters

    Electrical Input Voltage 3-phase 380V ±15% / 1-phase 220V ±10%
    Output Voltage 3-phase 0–380V (0–800Hz)
    Output Power Range 0.75–160kW (380V) / 0.75–22kW (220V)
    Overload Capacity 150% for 60s (G-type) / 120% for 60s (P-type)
    Control Control Modes Sensorless Vector (SVC)
    V/F Control
    Speed Regulation Range 1:100 (SVC) / 1:50 (V/F)
    Carrier Frequency 0.5–16kHz (adjustable)
    Torque Boost Auto or Manual (0.1–30.0%)
    I/O & Comm Digital Inputs 5 (1 high-speed pulse)
    Analog Inputs 2 (0–10V/0–20mA)
    Relay Outputs 2 (250V AC/3A)
    Communication RS485, Modbus-RTU
    Environment Operating Temperature -10°C to +40°C (derate 1.5%/°C >40°C)
    Storage Temperature -20°C to +60°C
    Humidity
    Altitude ≤1000m (no derate);
    >1000m: derate 1%/100m
    Protection Key Protections Overcurrent/voltage, Phase loss, Short circuit, Overheat, Ground fault
    Physical Installation Spacing (≥15kW) Side: ≥50mm;
    Top-bottom: ≥200mm (w/ baffle)
    Cooling Forced air (fan/AC required for enclosed cabinets)